1-4 Loop Fire Alarm Control Panel

The MxPro 4 series is fully expandable from 1 to 4 loops complete with 4 on-board sounder circuits. The control panel consists of a simple to use LCD menu driven graphical interface, dual, flash-based microprocessor technology driven by a 5 Amp power supply and charger approved to EN54 parts 2 & 4.

Dedicated system navigation keys makes learning this control panel user friendly as well as installer friendly due to the uncomplicated, trouble free, commissioning and fault finding.

Powerful Cause and Effect programming coupled with dynamic zoning makes the panel suitable for a wide range of site applications, from small to large complex multi area systems. Fully on site programmable via on board alphanumeric keypad or PC -NeT configuration tools.

An extensive suite of PC based, software programs have been developed to supplement the MxPro 4 series Fire panels.

 


Features

  • Fully expandable from 1 to 4 loops via common plug in loop driver boards.
  • Advanced graphical LCD user interface with up to 1000 fire zones as standard, allowing full EN54 compliance without additional hardware or LED indication.
  • 5 Amp power supply and charger to EN54 part 4.
  • Dedicated RS232 serial port for direct PC or modem connection.
  • Graphical display configurable for virtually any language
  • When connected to the fault tolerant Ad-NeT network, the panel operates as a true peer-to-peer interface (with up to 1000 shared zones) with full cross panel reporting, control functionality.
  • Installer friendly Auto-learn and Loop Detection facility for troublefree, commissioning. Fully on-site programmable via on-board alphanumeric keypad or PC configuration tools.


Key Features

Fully Expandable to 4 LoopsFully NetworkableOptional on-board printerOptional remote printer
EN54 Parts 2 & 4 ApprovedApollo & Hochik protocolArgus & Nittan protocolMultiple Languages
Dual microprocessorReal Time ClockGlobal Compliance3 Year warranty
Plug-in connectorsFlash memoryRobust equipment chassis
Specification
Base TechnologyDual Flash based Processors with Real Time Clock, ‘Trace’ diagnostics, ‘Pulse’ communications & programmable languages
DisplayBacklit 240 x 64 Graphical LCD
LED Indicators3 red (2 x Fire, 1 x Alarm), 1 green (Power) & 12 amber (Fault & System)
ControlsAlpha numeric keypad, navigation keys & system keys for reset, Mute, Silence/Resound & Evacuate
ProtocolsApollo (S90,XP95, Xplorer and Discovery), Hochiki ESP, Nittan Evo & Argus Vega
Number of Fire Zones1000 (200 per individual panel)
Number of loops1-4. Expandable via individual plug-in loop driver
Devices per loopAs per detector manufacturer’s specifications
Loop Current500mA
On Board Sounder circuits4 x 1 Amp programmable
On Board Relays2 x 1 Amp 30v AC/DC Programmable
Auxiliary Supply1 x 24v 500mA
Open Collector / Logic Outputs8 x programmable (via optional 8-way relay card)
Programmable Switch Inputs8 volt free digital inputs
On Board Power Supply4 Amp high efficiency switched mode
Mains Supply230 V Ac (+10%, -15% tolerance) 50 /60 Hz 1.9 Amp
Battery Capacity24v 18 Ah internal. 24v 48 Ah external
Charger Current2.0 Amp DDP monitored, temperature compensated integral charger
Serial ports1 RS232 onboard for PC, modem or external printer
ProgrammingVia on-board keypad or PC running Windows Tools
Event Log1000 Fire & Event + Diagnostic
NetworkingOptional plug in network card
Printer (Optional)Optional on-board or external serial printer
Enclosure / ColourSteel IP30 / beige (textured)
Cable Entry20mm Knock-outs. 18 x top, 9 x top rear and 2 x bottom
Size H x W x D mm / WeightAct475 x 450 x 115 / 10Kg, 475 x 450 x 188 / 10.5Kg (/D deeper enclosure). Back box only (when recessing) 475 x 450 x 100. Deeper back box only (when recessing) 475 x 450 x 173ual 24
Metalwork OptionsFlushing bezel, ancillary enclosure & battery box
ApprovalsBS EN54-2 & 4:1998

Order Codes and Options

Mx-4400*: 0 to 4 Loop Analogue Addressable - No loop cards
Mx-4401*: Mx-4400 c/w 1 Loop Card Fitted & Tested
Mx-4402*: Mx-4400 c/w 2 Loop Cards Fitted & Tested
Mx-4403*: Mx-4400 c/w 3 Loop Cards Fitted & Tested
Mx-4404*: Mx-4400 c/w 4 Loop Cards Fitted & Tested
Mx-4400*/D: 0 - 4 loop analogue addressable with Deeper Enclosure for 2 x 38AHr Batteries - No loop cards
Mx-4401*/D: Mx-4400 with Deeper Enclosure for 2 x 38AHr Batteries - 1 loop card fitted and tested
Mx-4402*/D: Mx-4400 with Deeper Enclosure for 2 x 38AHr Batteries - Two loop cards fitted and tested
Mx-4403*/D: Mx-4400 with Deeper Enclosure for 2 x 38AHr Batteries - Three loop cards fitted and tested
Mx-4404*/D: Mx-4400 with Deeper Enclosure for 2 x 38AHr Batteries - Four loop cards fitted and tested
Mx-4400*/R: Mx-4400 chassis c/w 19 inch rack mounting bezel - no loop cards
Mx-4400*/LE: Mx-4400 in large deep enclosure (950mm high) - no loop cards
* Add /N: for Nittan Evolution Protocol
* Add /V: for Argus Vega Protocol