Specification
|
---|
Base Technology | Dual flash based processors with real time clock, trace diagnostics, pulse communications & programmable languages |
Display | Backlit 240 x 64 Graphical LCD |
LED Indicators | 3 red (2 x Fire, 1 x Alarm), 1 green (Power) & 12 amber (Fault & System) |
Controls | Alpha numeric keypad, navigation keys & system keys for Reset, Mute, Silence/Resound & Evacuate |
Protocols | Apollo (S90,XP95, Xplorer and Discovery), Hochiki ESP, Nittan Evolution & Argus Vega |
Number of Fire Zones | 1000 (200 per individual panel) |
Number of loops | 1-2. Expandable via individual plug-in loop driver |
Devices per loop | As per detector manufacturer’s specifications |
Loop Current | 500mA |
On Board Sounder circuits | 2 x 1 Amp programmable |
On Board Relays | 2 x 1 Amp 30v AC/DC programmable |
Auxiliary Supply | 1 x 24v 500mA |
Open Collector / Logic Outputs | 8 x programmable (via optional 8-way relay card) |
Programmable Switch Inputs | 8 volt free digital inputs |
On Board Power Supply | 4 Amp high efficiency switched mode |
Mains Supply | 230 V Ac (+10%, -15% tolerance) 50 /60 Hz 1.9 Amp |
Battery Capacity | 24v 18 Ah internal. 24v 48 Ah external |
Charger Current | 2.0 Amp DDP monitored, temperature compensated integral charger |
Serial ports | 1 RS232 onboard for PC, modem or external printer |
Programming | Via on-board keypad or PC running Windows tools |
Event Log | 1000 Fire & Event + Diagnostic |
Networking | Optional plug in network card |
Printer (Optional) | Optional on-board or external serial printer |
Enclosure / Colour | Steel IP30 / beige (textured) |
Cable Entry | 20mm knock-outs. 18 x top, 9 x top rear and 2 x bottom |
Size H x W x D mm / Weight | Actual 475 x 450 x 115 / 10Kg, 475 x 450 x 188 / 10.5Kg (/D deeper enclosure). Back box only (when recessing) 475 x 450 x 100. Deeper back box only (when recessing) 475 x 450 x 173 |
Metalwork Options | flushing bezel, ancillary enclosure & battery box |