Single Loop Fire Alarm Control Panel

The MxPro 4 comes fitted complete with an internal loop driver card (Apollo/Hochiki only) and 2 on-board sounder circuits. The control panel consists of a simple to use LCD menu driven graphical interface, dual, flash-based microprocessor technology driven by an board 24V DC, 2 Amp high efficiency switched mode power supply and charger approved to EN54 parts 2 & 4.

Dedicated system navigation keys makes this control panel user friendly as well as installer friendly due to the uncomplicated, trouble-free, commissioning and fault finding.

Powerful cause and effect programming coupled with dynamic zoning makes the panel suitable for a wide range of site applications, from small to large complex multi-area systems. Fully on-site programmable via on board alphanumeric keypad or PC-NeT configuration tools.

An extensive suite of PC based, software programs have been developed to supplement the MxPro 4 series fire panels.


Features

  • Full support of Apollo (Discovery, Xplorer S90 & XP95) , Hochiki ESP protocols.
  • Advanced graphical LCD user interface with up to 250 fire zones as standard, allowing full EN54 compliance without additional hardware or LED indication.
  • Dedicated RS232 serial port for direct PC or modem connection.
  • Installer friendly auto-learn and loop detection facility for uncomplicated, trouble-free, commissioning and fault finding.
  • Fully on-site programmable via on-board alphanumeric keypad or PC configuration tools.
  • Flash memory and the advanced graphical display enables the panels to be configured to operate in virtually any language with any character set and allows the installer's logo and company details to be applied to the LCD display.
  • Robust, removable equipment chassis with plug-in connectors for simple fixing and cable termination.
  • When connected to the fault tolerant Ad-NeT network, the panel operates as a true peer-to-peer interface with full cross-panel reporting, control and cause-and-effect functionality.


Key Features

Single loop control panelEN54 Parts 2 & 4 approvedApollo/Hochiki protocol3 Year warranty
Global complianceMultiple languagesFully networkableInternal loop card
Optional remote printerDual microprocessorReal time clockUp to 1000 shared zones
Specification
Base technologyDual-flash based processors with real time clock, trace diagnostics, pulse communications & programmable languages
DisplayBacklit 240x64 graphical LCD
LED indicators3 red (2 x Fire, 1 x Alarm), 1 green (Power) & 12 amber (Fault & System)
ControlsAlpha-numeric keypad, navigation keys & system keys for reset, mute, silence/resound & evacuate
ProtocolsApollo (S90,XP95, Xplorer and Discovery), Hochiki ESP, Nittan Evolution & Argus Vega
Number of fire zones250 (100 per individual panel)
Number of loops1
Devices per loopAs per detector manufacturer’s specifications
Loop current500mA
On board sounder circuits2 x 1 Amp programmable
On board relays2 x 1 Amp 30v AC/DC programmable
Auxiliary supply1 x 24v 500mA
Open collector / logic outputs2 x programmable (via optional 2-way relay card)
Programmable switch inputs8 volt free digital inputs
Total available output current2 Amps maximum available for loop current + sounder outputs + auxiliary supply
Mains supply230 V 50 Hz AC (+10%, -15% tolerance) 0.4 Amp
Battery capacity24v 7 Ah internal. 24v 12 Ah external
Charger current0.4 Amp DDP monitored, temperature compensated integral charger
Serial ports1 RS232 Onboard for PC, modem or external printer
ProgrammingVia on-board keypad or PC running Windows Tools
Event log1000 fire & event + diagnostic
NetworkingOptional plug in network card
Printer (optional)External serial printer
Enclosure / colorSteel IP30 / beige (textured)
Cable entry20mm knock-outs. 7 x top, 7 x top rear
Size H x W x D mm / weightMx-4100: 320 x 345 x 85 / 6 Kg
 Mx-4100/L or /LG: 340 x 355 x 125 / 7Kg
Metalwork optionsMx-4100: Back box only (when recessing) 320 x 345 x 70 / 2Kg
 Mx-4100/L or /LG: Back box only (when recessing) 340 x 355 x 100 / 3Kg
 Flushing bezel, battery box and a range of special finishes including stainless steel, brass and chrome
ApprovalsBS EN54-2:1998, BS EN 54-4:1998

Order Codes and Options

Mx-4100: Single loop analogue addressable
Mx-4100L: Single loop analogue addressable c/w lockable hinged door
Mx-4100/LG: Single loop analogue addressable c/w lockable hinged door & perspex kit
Mxp-024(F)*: 20 zone LED card for Mx-4100
Mxp-003(F)*: Standard network card
Mxp-009(F)*: Fault Tolerant network card
Mxm-001: Semi-flushing bezel for Mx-4100
Mxm-037: Semi-flushing bezel for Mx-4100L / LG
(F)*: Add - Fitted